Product Description
Key Features
• Easy to operate : next-generation graphical LCD display
• 1 slot for optional communication card
• Long backup time with up to 4 optional EBM
• Internal bypass allows service continuity in case of UPS fault
• Constantly monitors power conditions and regulates voltage and frequency
• Advanced Battery Management (ABM) technology to increase battery lifetime
Eaton 9SX 6000VA UPS
Eaton 9SX UPS, AU, Tower, 6000VA, 5400W, 240VAC, Input: Hardwire, Output: hardwire, built-in battery, Multilingual graphical LCD display
Specifications
Topology | Online/Double-conversion |
Form factor | Tower |
Construction type | Free standing model |
Color | Black |
VA rating | 6000 VA |
Wattage | 5400 W |
Internal bypass | Yes |
Hot swap power | No |
Auto shutdown function | Yes |
Input nominal voltage | 240V |
Nominal frequency | 50/60 Hz |
Input frequency range | 40-70 Hz |
Receptacle | hardwire |
Output waveform | Sine wave |
Voltage | 240V |
Output nominal voltage | 240V |
Voltage type | AC |
Runtime graph | View runtime graph |
Battery replacement | Hot swappable |
Battery type | Sealed, lead-acid |
Extended battery capability | Yes |
Expansion slots | One slot for optional communication card |
Includes network card | No |
Software compatibility | Eaton Intelligent Power Manager, Eaton Intelligent Power Protector |
User interface | Multilingual graphical LCD display |
Altitude | <1000m for nominal power, 10% power degrading every 1000m (up to 3000m) |
Noise level | <45 dB at 1 meter |
Relative humidity | 0-96% non-condensing |
Temperature range | 0° to 40°C (32° to 104°F) |
Input voltage range | 180-276 Vac without derating (up to 120-276 Vac with derating) |
Output frequency | 50/60 Hz |
Output power factor | 0.9 |
Phase (INPUT) | Single-phase |
Phase (OUTPUT) | Single-phase |
General |
|
Dimensions (WxHxD) | 542 x 575 x 244 mm |
Weight | 65.5kg |
Compliances | CE Marked RCM CB |
Certifications | IEC 61000-4 IEC/EN 62040-2 IEC/EN 62040-1 EN 62040-3 |