Product Description
Key Features
• Surge suppression rating 40kA all modes
• Small footprint, modular design
• Protection Fail Indicators
• 3 mode, 3 Stage Protection
• Enclosed in rugged metal housing
• Surge suppression & filtering in a single package
Eaton PSFi Series
Designed for IEC, Class III, plug in surge power board for domestic, SOHO and light industrial environments.10A and 16A IEC in / out, rugged case, dual mode filter and 3 mode surge protection.
Specifications
Technical | PSF10I | PSF16I |
Number of ports | 2 Port | |
Method of mounting | Portable | |
Input voltage - Uc | 200-250VAC 1 Phase | |
Maximum Continuous voltage - MCOV | 320VAC L-N | |
Temporary overvoltage - TOV | 350VAC L-N, 15 mins | |
Service type | TT, TN, TN C-S or any 1 phase system with a grounded neutral. This unit must not be connected to an ungrounded system. | |
Test Classification | Class II | |
Current rating - continuous | 10A | 16A |
Test Classification | Class III (IEC 61643-1), Category A (ANSI/IEEE C62.41) | |
Recommended max. overcurrent protection | 10A | 16A |
Residual current | <0.5 mA | |
Protection modes | Line-Neutral, Line-Earth, Neutral-Earth | |
In 8/20us (Line-Neutral) Nominal surge life | 20kA x 15 hits | |
In 8/20us (Line-Earth) Nominal surge life | 3kA x 20 hits | |
In 8/20us (Neutral-Earth) Nominal surge life | 3kA x 20 hits | |
Ismax 8/20us (Line-Neutral) Max surge level | 40kA | |
Ismax 8/20us (Line-Earth) Max surge level | 10kA | |
Ismax 8/20us (Neutral-Earth) Max surge level | 10kA | |
Filter attenuation | 40dB nominal above 1MHz | |
Initial clamp voltage (Line-Neutral) | 560V (350VAC RMS) | |
Initial clamp voltage (Line-Earth) | 680V (420VAC RMS) | |
Initial clamp voltage (Neutral-Earth) | 680V (420VAC RMS) | |
Residual voltage (Vpl) (Line-Neutral) (Let through voltage) | <900 (3kA, 8/20uS) | |
Internal protection (fusing) | Thermal fusing on primary line-connected MOVs | |
Terminations | IEC 320-C14 10A input x 1, IEC 320-C13 10A output x 1 | IEC 320-C20 16A input x 1, IEC 320-C19 16A output x 1 |
Alarms/indicators | 2 LED display, Power OK, Protection Fault | |
Location Category | Indoor | |
Enclosure rating | IP24 | |
Design Standards: | IEC61643-1, IEC610006-1, 2, 3, 4 ANSI/IEEE C62.41 Cat B, C, D, E AS1768-2007 Cat B, C, D, E AS3000, AS3100, CE mark | |
Dimensions& Weight | 90 x 205 x 55 mm (W x D x H), 1kg | |
Environment | -10 to 50oC, 0 to 95% RH (non-condensing) |