Product Description
Key Features
• 2 Australian sockets and 3 x 10 Amp IEC outlets
• Free, programmable Power Management
• Emergency Power Off Function
• Output Power Factor 0.9
• ECO Mode; Smart AVR; Pure Sine Wave Output
• Multiple Communication Available with faster SNMP Card
• Ultra Modern, Informative LCD – Shows Battery Time Remaining
PowerShield Commander Tower 1100VA
The new Commander Tower has been developed to provide a better power factor with an all new, modern design and ultra modern, informative LCD display.
Visit the PowerShield UPS Sizing Guide. which will help you select the correct UPS for your power protection needs.
Specifications
COMMANDER TOWER |
|||
MODEL | Commander 1100 | Commander 2000 | |
Model Number | PSCM1100 | PSCM2000 | |
Capacity (PF = 0.9) | 1100 VA / 990 W | 2000 VA / 1800 W | |
INPUT |
|||
Nominal Voltage | 240Vac | ||
Acceptable Voltage Range | 162-290 VAC | ||
Frequency Range | 50/60Hz ± 5Hz (auto sensing) | ||
OUTPUT |
|||
Voltage Regulation (AC Mode) | 240Vac (Selectable 208/220/230Vac) ± 10% AVR | ||
Voltage Regulation (Batt. Mode) | ± 1.5% (before battery alarm) | ||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | ||
Current Crest Ratio | 3:1 | ||
Total Harmonic Distortion | 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) | ||
Transfer Time | 6ms (Typical), 10ms max. | ||
Waveform (Batt. Mode) | Pure Sine Wave | ||
IEC Outlets | 10A, C13 x 3 | ||
Australian Sockets | 2 | ||
EFFICIENCY |
|||
AC Mode | 98% (Advanced ECO design) | ||
Battery Mode | 89% | 91% | |
BATTERY |
|||
Standard Model | Battery Type & Number | 12V / 9AH (x2) | 12V / 9AH (x4) |
Recharge Time | 4 hours recover to 90% capacity | ||
PROTECTION |
|||
Full Protection | Overload, thermal, short circuit, discharge and overcharge protection | ||
Surge Protection | 1968 Joules / 39000 Amps | ||
ENVIRONMENT |
|||
Operation Temperature | 0 - 40°C | ||
Relative Humidity | 0-90% (RH non-condensing) | ||
Noise Level | < 45dB | ||
COMMUNICATIONS & MANAGEMENT |
|||
Interface | USB and RS-232 as standard, Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact | ||
Software | PowerShield NetGuard® software - supports Windows based operating system, Linux, Unix and Mac | ||
HID | Supports Windows, Apple, Linux, NAS and various industrial controllers | ||
LCD Display/Alarm | AC mode, Batt. Mode, Load Level, Input Voltage, Output Voltage, Overload, Fault, Battery Replacement, Low Batt., Batt. Time Remaining | ||
Audible Alarm | Battery Mode, Low Battery (Batt. Mode), Battery Replacement, Fault, Overload | ||
PHYSICAL |
|||
Standard Model | Dimension D x W x H (mm) | 397 x 145 x 220 | 455 x 145 x 220 |
Weight Nett/Gross (kg) | 12.9 / 14.4 | 20.5 / 22.5 | |
COMPLIANCE |
|||
Safety | EN62040-1 -1 2003, IEC 60950-1 -1 | ||
EMC | EN62040-2 2006 | ||
RoHS | Directive 2011/65/EU |
* Specifications are subject to change without notice.